INES 0

ONE CONTROL ROD NOT FULLY INSERTED AFTER SCRAM

On August 22 when Ringhals 4 was operating at 51% with one turbine, the power supply to 400 kV grid was interrupted for 9 minutes. The transition to house load operation failed and Ringhals 4 scrammed. At the scram a control rod did not reach the bottom but jammed 18 steps from a wholly inserted position. (The whole insert in the position is 228 step).
At the subsequently performed drop test the same rod jammed 24 steps from a wholly inserted position. The drop tests also revealed that another 3 control rods jammed between 6 and 12 steps out (the total number of control rods is 48). All 4 rods are placed in fuel assemblies which were placed into the core 1991.
Investigation about the cause of the jammed control rods in the guide tubes proceed.
Table II, Severity classification criteria for degradation of defence in depth with an initiator.
Safety function availability: full, initiator frequency: high/expected, INES scale 0.

Location: RINGHALS-4
Event date: Mon, 22-08-1994